EMERSON IC200ALG263 (United States)

본문 바로가기
Member
장바구니0

장바구니

  • 해당내용 없음
장바구니 바로가기
위시리스트0
Search
icon
오늘본상품1

오늘 본 상품

  • EMERSON IC
    US$ 875.00

EMERSON

사용후기 0 위시리스트저장 0

EMERSON IC200ALG263

GE Fanuc (EMERSON) IC200ALG263 analog input module uses 15 single-ended channels for precise –10 VDC to +10 VDC signal acquisition in industrial automation systems. The module features 15-bit resolution, 100 kΩ input impedance, and a 7.5 ms update rate; review technical specifications and troubleshooting and compatibility guidelines now.
EMERSON: Product Insights  |  EMERSON: Technical Guides

상품 선택옵션 0 개, 추가옵션 0 개

Price US$875.00
Shipping Fee Paid at Checkout
Brand EMERSON
Model IC200ALG263
Availability In stock

선택된 옵션

  • EMERSON IC200ALG263
    +US$0.00
* Customs duties and VAT incurred during import clearance are the buyer's responsibility and are not included in the total amount.
위시리스트

상품 정보

상품 상세설명

OVERVIEW

Official designation: GE Fanuc IC200ALG263 (VersaMax, Analog Input Module)

Role/Application: High-density module for the VersaMax system, acquiring 15 single-ended analog voltage signals in the bipolar -10 VDC to +10 VDC range.

KEY SPECS SUMMARY

Power: 150 mA at 5V DC from backplane

Interfaces / Ports: 15 single-ended inputs

Indicators: OK LED

Operating Temp: 0 degrees C to 60 degrees C

Platform / Compatibility: VersaMax I/O and Control System

Limit: Input impedance 100 kOhms minimum

Lifecycle: Active

FREQUENTLY ASKED QUESTIONS

Technical Specifications:

Q: What is the maximum continuous isolation voltage for the user inputs to the logic circuitry?

A: The module provides continuous isolation of 250V AC from user input to logic.

Wiring & Installation:

Q: Is an external power supply required for the IC200ALG263 module operation?

A: No, the module receives all operating power from the VersaMax backplane power supply.

Troubleshooting & Compatibility:

Q: What action should be taken if the green OK LED turns off and a hardware error is reported?

A: Power cycle the IC200ALG263 module or replace it to clear the detected internal hardware error.

Replacement & Upgrades:

Q: What is the maximum accuracy of the voltage measurement across the operating temperature range?

A: The maximum accuracy is plus or minus 1 percent of full scale across the 0 to 60 degrees C range.

상품 정보 고시

Category Details
Product Name See this page for details
Model Name See this page for details
Certification or Licensing Information Required by Law See this page for details
Country of Manufacture or Origin See this page for details
Manufacturer See this page for details
After-sales Service Contact or Customer Support Number See this page for details

사용후기

등록된 사용후기

Be the first to leave a review!

상품문의

등록된 상품문의

Be the first to ask a question about this product!

배송정보

Service Information
 

교환/반품

Caution When Purchasing