EMERSON IC200ALG263

GE Fanuc (EMERSON) IC200ALG263 analog input module uses 15 single-ended channels for precise –10 VDC to +10 VDC signal acquisition in industrial automation systems. The module features 15-bit resolution, 100 kΩ input impedance, and a 7.5 ms update rate; review technical specifications and troubleshooting and compatibility guidelines now.
EMERSON: Product Insights  |  EMERSON: Technical Guides

상품 선택옵션 0 개, 추가옵션 0 개

가격 US$875.00
배송비 주문 시 결제
브랜드 EMERSON
모델명 IC200ALG263
상태 판매 중

선택된 옵션

  • EMERSON IC200ALG263
    +US$0.00
* 통관 과정에서 발생하는 관세 및 부가가치세는 구매자 부담이며, 총 결제금액에 포함되어 있지 않습니다.
위시리스트

상품 정보

상품 상세설명

OVERVIEW

Official designation: GE Fanuc IC200ALG263 (VersaMax, Analog Input Module)

Role/Application: High-density module for the VersaMax system, acquiring 15 single-ended analog voltage signals in the bipolar -10 VDC to +10 VDC range.

KEY SPECS SUMMARY

Power: 150 mA at 5V DC from backplane

Interfaces / Ports: 15 single-ended inputs

Indicators: OK LED

Operating Temp: 0 degrees C to 60 degrees C

Platform / Compatibility: VersaMax I/O and Control System

Limit: Input impedance 100 kOhms minimum

Lifecycle: Active

FREQUENTLY ASKED QUESTIONS

Technical Specifications:

Q: What is the maximum continuous isolation voltage for the user inputs to the logic circuitry?

A: The module provides continuous isolation of 250V AC from user input to logic.

Wiring & Installation:

Q: Is an external power supply required for the IC200ALG263 module operation?

A: No, the module receives all operating power from the VersaMax backplane power supply.

Troubleshooting & Compatibility:

Q: What action should be taken if the green OK LED turns off and a hardware error is reported?

A: Power cycle the IC200ALG263 module or replace it to clear the detected internal hardware error.

Replacement & Upgrades:

Q: What is the maximum accuracy of the voltage measurement across the operating temperature range?

A: The maximum accuracy is plus or minus 1 percent of full scale across the 0 to 60 degrees C range.

상품 정보 고시

Category Details
Product Name See this page for details
Model Name See this page for details
Certification or Licensing Information Required by Law See this page for details
Country of Manufacture or Origin See this page for details
Manufacturer See this page for details
After-sales Service Contact or Customer Support Number See this page for details

사용후기

등록된 사용후기

Be the first to leave a review!

상품문의

등록된 상품문의

Be the first to ask a question about this product!

배송정보

Service Information
 

교환/반품

Caution When Purchasing