IC693MDL390 Isolated Output Module provides 5 channels of 85–264 VAC switching with an individual maximum output of 2.0 amperes per point. GE Fanuc (EMERSON) Series 90-30 PLC ensures reliable performance with total module output ratings of 5 amperes at 45 C, access detailed technical specifications for optimal wiring and installation.
EMERSON: Product Insights  |  EMERSON: Technical Guides

상품 선택옵션 0 개, 추가옵션 0 개

Price US$1,475.00
Shipping Fee Paid at Checkout
Brand EMERSON
Model IC693MDL390
Availability In stock

선택된 옵션

  • EMERSON IC693MDL390
    +US$0.00
* Customs duties and VAT incurred during import clearance are the buyer's responsibility and are not included in the total amount.
위시리스트

상품 정보

상품 상세설명

OVERVIEW

Official designation: GE Fanuc IC693MDL390 (Series 90-30, Isolated AC Output Module)

Role/Application: A 5-point isolated AC output module for the Series 90-30 PLC, capable of switching 85–264 VAC loads with a high inrush capacity for inductive and incandescent devices.

KEY SPECS SUMMARY

Power: 110 mA from 5 VDC backplane

Interfaces / Ports: 20-pin terminal block

Indicators: Five green LEDs (A1-A5) and one red "F" LED

Operating Temp: 0 to 60 degrees C

Platform / Compatibility: GE Fanuc Series 90-30 PLC

Limit: 5 A maximum per module at 45 degrees C

Lifecycle: Discontinued by manufacturer

FREQUENTLY ASKED QUESTIONS

Technical Specifications:

Q: What is the maximum inrush current capacity and the output voltage drop of this module?

A: Maximum inrush current is 25 A for one cycle, with a maximum output voltage drop of 1.5 volts.

Wiring & Installation:

Q: What is the significance of the red "F" indicator light on the output module?

A: The red "F" LED serves as a blown fuse indicator for any of the five output circuits.

Troubleshooting & Compatibility:

Q: What are the maximum output leakage current values at 120 VAC and 240 VAC?

A: Maximum leakage current is 3 mA at 120 VAC and 6 mA at 240 VAC output voltage.

Replacement & Upgrades:

Q: What is the maximum output current rating per module when operating at 60 degrees C?

A: The total output current must not exceed 2.0 A per module when operating at 60 degrees C.

상품 정보 고시

Category Details
Product Name See this page for details
Model Name See this page for details
Certification or Licensing Information Required by Law See this page for details
Country of Manufacture or Origin See this page for details
Manufacturer See this page for details
After-sales Service Contact or Customer Support Number See this page for details

사용후기

등록된 사용후기

Be the first to leave a review!

상품문의

등록된 상품문의

Be the first to ask a question about this product!

배송정보

Service Information
 

교환/반품

Caution When Purchasing