EMERSON IC693MDL916 (United States)

본문 바로가기
Member
장바구니0

장바구니

  • 해당내용 없음
장바구니 바로가기
위시리스트0
Search
icon
오늘본상품1

오늘 본 상품

  • EMERSON IC
    US$ 1,375.00

EMERSON

사용후기 0 위시리스트저장 0

EMERSON IC693MDL916

IC693MDL916 Relay Output Module delivers 16 Form A isolated contacts, supporting a 4 amperes max current rating across 5–250 VAC or 5–125 VDC. GE Fanuc (EMERSON) Series 90-30 PLC ensures flexible load control, drawing only 300 mA from the 5 VDC backplane, review replacement and upgrades paths and wiring and installation documentation for reliable operation.
EMERSON: Product Insights  |  EMERSON: Technical Guides

상품 선택옵션 0 개, 추가옵션 0 개

Price US$1,375.00
Shipping Fee Paid at Checkout
Brand EMERSON
Model IC693MDL916
Availability In stock

선택된 옵션

  • EMERSON IC693MDL916
    +US$0.00
* Customs duties and VAT incurred during import clearance are the buyer's responsibility and are not included in the total amount.
위시리스트

상품 정보

상품 상세설명

OVERVIEW

Official designation: GE Fanuc IC693MDL916 (Series 90-30, Isolated Relay Output Module)

Role/Application: A 16-point isolated relay output module providing Form A (normally open) contacts for switching AC or DC loads in the Series 90-30 PLC system.

KEY SPECS SUMMARY

Power: 300 mA at 5 VDC

Interfaces / Ports: 24-pin terminal strip

Indicators: 16 LEDs for channel status

Operating Temp: 0 to 60 degrees C

Platform / Compatibility: GE Fanuc Series 90-30 PLC

Limit: 4 A maximum per point, 16 A maximum total

Lifecycle: Discontinued by manufacturer

FREQUENTLY ASKED QUESTIONS

Technical Specifications:

Q: What are the maximum voltage ratings for AC and DC switching supported by the relay contacts?

A: The contacts support switching up to 250 VAC and 125 VDC maximum.

Wiring & Installation:

Q: What is the recommended fuse rating for protecting the output contacts on this module?

A: Refer to the latest manufacturer manual.

Troubleshooting & Compatibility:

Q: How is the 16 A maximum current limit distributed across the 16 output points?

A: The module has four groups of four outputs, each group is limited to 4 amperes.

Replacement & Upgrades:

Q: What are the typical mechanical life and electrical life ratings for the relay contacts?

A: Mechanical life is 20 million operations; electrical life is 100 thousand operations minimum.

상품 정보 고시

Category Details
Product Name See this page for details
Model Name See this page for details
Certification or Licensing Information Required by Law See this page for details
Country of Manufacture or Origin See this page for details
Manufacturer See this page for details
After-sales Service Contact or Customer Support Number See this page for details

사용후기

등록된 사용후기

Be the first to leave a review!

상품문의

등록된 상품문의

Be the first to ask a question about this product!

배송정보

Service Information
 

교환/반품

Caution When Purchasing