GE Fanuc (EMERSON) IC694MDL742 output module features 16 points in two groups with ESCP per group for enhanced operational safety and signal distribution. The RX3i unit provides 12/24 VDC output, 0.5 A per point, and 110 mA @ 5 VDC power, check technical specifications and wiring and installation details for dependable and stable PLC integration.
EMERSON: Product Insights  |  EMERSON: Technical Guides

상품 선택옵션 0 개, 추가옵션 0 개

Price US$866.67
Shipping Fee Paid at Checkout
Brand EMERSON
Model IC694MDL742
Availability In stock

선택된 옵션

  • EMERSON IC694MDL742
    +US$0.00
* Customs duties and VAT incurred during import clearance are the buyer's responsibility and are not included in the total amount.
위시리스트

상품 정보

상품 상세설명

OVERVIEW

Official designation: GE Fanuc IC694MDL742 (PACSystems RX3i, DC Output Module)

Role/Application: 16-point positive logic output module with Electronic Short Circuit Protection (ESCP) for switching 12/24 VDC loads and supporting hot-swap in the RX3i system.

KEY SPECS SUMMARY

Power: 130 mA from 5V bus (all outputs on)

Interfaces / Ports: Terminal block interface

Indicators: 16 individual LEDs, one red Fault LED

Operating Temp: 0 degrees C to 60 degrees C

Platform / Compatibility: PACSystems RX3i Universal Backplane

Limit: 1 Amp maximum per point, 4 Amps max per group at 50 degrees C

Lifecycle: Active or Discontinued, varies by model/revision

FREQUENTLY ASKED QUESTIONS

Technical Specifications:

Q: What is the continuous isolation voltage between the field and the backplane?

A: Isolation is 250 Volts AC continuous between the field and backplane.

Wiring & Installation:

Q: What is the purpose of the two groups of eight outputs on the module?

A: Each group operates independently with its own ESCP and common power terminal.

Troubleshooting & Compatibility:

Q: What devices are compatible with this module's positive logic outputs?

A: Compatible loads include solenoids, motor starters, and indicator lights.

Replacement & Upgrades:

Q: What is the consequence of a short circuit on an output point protected by ESCP?

A: The affected output point turns off, and the red Fault LED activates.

상품 정보 고시

Category Details
Product Name See this page for details
Model Name See this page for details
Certification or Licensing Information Required by Law See this page for details
Country of Manufacture or Origin See this page for details
Manufacturer See this page for details
After-sales Service Contact or Customer Support Number See this page for details

사용후기

등록된 사용후기

Be the first to leave a review!

상품문의

등록된 상품문의

Be the first to ask a question about this product!

배송정보

Service Information
 

교환/반품

Caution When Purchasing