EMERSON IC200MDL331

GE Fanuc (EMERSON) IC200MDL331 discrete output module features 8 isolated AC outputs for high-capacity 120 VAC switching of loads such as solenoids and contactors. The module provides 2.0 A per point capacity over 85–132 VAC, consuming 85 mA backplane current; examine the technical specifications and wiring and installation guide now.
EMERSON: Product Insights  |  EMERSON: Technical Guides

상품 선택옵션 0 개, 추가옵션 0 개

Price US$1,408.33
Shipping Fee Paid at Checkout
Brand EMERSON
Model IC200MDL331
Availability In stock

선택된 옵션

  • EMERSON IC200MDL331
    +US$0.00
* Customs duties and VAT incurred during import clearance are the buyer's responsibility and are not included in the total amount.
위시리스트

상품 정보

상품 상세설명

OVERVIEW

Official designation: GE Fanuc IC200MDL331 (VersaMax, Discrete Output Module)

Role/Application: Provides 8 individually isolated output channels for switching 120 VAC loads like solenoids or contactors in industrial systems.

KEY SPECS SUMMARY

Power: 85 mA maximum from backplane

Interfaces / Ports: Requires IC200CHS carrier

Indicators: One LED per point, plus OK LED

Operating Temp: 0 degrees C to 60 degrees C

Platform / Compatibility: VersaMax Control System

Limit: 2.0A maximum per point, 20A inrush

Lifecycle: Active

FREQUENTLY ASKED QUESTIONS

Technical Specifications:

Q: What is the continuous isolation rating between the user outputs and logic or frame ground?

A: Continuous isolation is rated for 250 VAC between the user outputs and module logic or frame ground.

Wiring & Installation:

Q: What external power supply voltage range is required for the output points?

A: The external power supply must be 85 to 132 VAC with a frequency range of 47 to 63 Hz.

Troubleshooting & Compatibility:

Q: What protection is built into the module for the isolated 120 VAC output channels?

A: Each output channel includes internal snubber and MOV components for protection.

Replacement & Upgrades:

Q: Is external suppression recommended when connecting the outputs to inductive loads?

A: Yes, use of external suppression circuits is highly recommended for inductive loads like contactor coils.

상품 정보 고시

Category Details
Product Name See this page for details
Model Name See this page for details
Certification or Licensing Information Required by Law See this page for details
Country of Manufacture or Origin See this page for details
Manufacturer See this page for details
After-sales Service Contact or Customer Support Number See this page for details

사용후기

등록된 사용후기

Be the first to leave a review!

상품문의

등록된 상품문의

Be the first to ask a question about this product!

배송정보

Service Information
 

교환/반품

Caution When Purchasing