EMERSON IC200MDL330

GE Fanuc (EMERSON) IC200MDL330 discrete output module features 16 isolated AC outputs for dependable 120 VAC switching of loads such as relays and contactors. The module operates across 85–132 VAC with 0.5 A per point capacity and 140 mA backplane consumption; examine the technical specifications and wiring and installation guide now.
EMERSON: Product Insights  |  EMERSON: Technical Guides

상품 선택옵션 0 개, 추가옵션 0 개

Price US$1,358.33
Shipping Fee Paid at Checkout
Brand EMERSON
Model IC200MDL330
Availability In stock

선택된 옵션

  • EMERSON IC200MDL330
    +US$0.00
* Customs duties and VAT incurred during import clearance are the buyer's responsibility and are not included in the total amount.
위시리스트

상품 정보

상품 상세설명

OVERVIEW

Official designation: GE Fanuc IC200MDL330 (VersaMax, Discrete Output Module)

Role/Application: Provides 16 individually isolated channels for switching 120 VAC loads, supporting relays, contactors, and indicators in the VersaMax system.

KEY SPECS SUMMARY

Power: 140 mA maximum from backplane

Interfaces / Ports: Requires IC200CHS carrier

Indicators: 16 individual LEDs, 1 OK LED

Operating Temp: 0 degrees C to 60 degrees C

Platform / Compatibility: VersaMax Control System

Limit: 0.5A per point, 5.0A inrush for one cycle

Lifecycle: Active

FREQUENTLY ASKED QUESTIONS

Technical Specifications:

Q: What is the continuous isolation voltage rating between the output points?

A: Continuous point to point isolation is rated for 250 VAC.

Wiring & Installation:

Q: What are the minimum and maximum recommended load current ratings per output point?

A: The minimum load current is 10 mA, and the maximum load current is 0.5 A per point.

Troubleshooting & Compatibility:

Q: What internal protection components are included on each 120 VAC output channel?

A: Each output channel is protected by both internal snubber and MOV components.

Replacement & Upgrades:

Q: Are external suppression circuits necessary for the module when switching inductive loads?

A: Yes, use of external suppression circuits is highly recommended for all inductive output loads.

상품 정보 고시

Category Details
Product Name See this page for details
Model Name See this page for details
Certification or Licensing Information Required by Law See this page for details
Country of Manufacture or Origin See this page for details
Manufacturer See this page for details
After-sales Service Contact or Customer Support Number See this page for details

사용후기

등록된 사용후기

Be the first to leave a review!

상품문의

등록된 상품문의

Be the first to ask a question about this product!

배송정보

Service Information
 

교환/반품

Caution When Purchasing