Emerson IC200ALG320 4-point Analog Current Output Module provides accurate 4–20 mA signals for process automation, featuring 4 uA resolution and 0.3 ms update rate. Its robust design ensures 1500 V isolation and 0.3 percent accuracy over a 50 to 500 ohms load, access technical specifications and wiring and installation details now.
EMERSON: Product Insights  |  EMERSON: Technical Guides

상품 선택옵션 0 개, 추가옵션 0 개

Price US$1,283.33
Shipping Fee Paid at Checkout
Brand EMERSON
Model IC200ALG320
Availability In stock

선택된 옵션

  • EMERSON IC200ALG320
    +US$0.00
* Customs duties and VAT incurred during import clearance are the buyer's responsibility and are not included in the total amount.
위시리스트

상품 정보

상품 상세설명

OVERVIEW

Official designation: Emerson IC200ALG320 (VersaMax, Analog Current Output Module)

Role/Application: A 4-channel, 12-bit analog current source module designed for industrial process automation, providing precise 4-20 mA control signals.

KEY SPECS SUMMARY

Power: 50 mA from +5V bus

Interfaces / Ports: Compatible with VersaMax carriers

Indicators: FLD PWR, OK LEDs

Operating Temp: 0 degrees C to 60 degrees C

Platform / Compatibility: VersaMax I/O system

Limit: 0.3 percent typical accuracy

Lifecycle: Active

FREQUENTLY ASKED QUESTIONS

Technical Specifications:

Q: What is the true digital resolution and the maximum current capability of the module?

A: The module has a 12-bit resolution with an over-range output up to 20.38 mA per channel.

Wiring & Installation:

Q: What is the recommended wire type and how should its shielding be terminated?

A: Shielded twisted cable is recommended; the shield connects directly to the carrier if supported by the wiring table.

Troubleshooting & Compatibility:

Q: What is the function of the FLD PWR LED and how can output behavior be configured on PLC stop?

A: FLD PWR indicates external field power; a jumper sets outputs to hold last state or default to 4 mA on PLC stop.

Replacement & Upgrades:

Q: What is the minimum external voltage supply and the typical isolation rating for the IC200ALG320?

A: External power must be 18 to 30 VDC, and isolation is 1500 VAC for one minute.

상품 정보 고시

Category Details
Product Name See this page for details
Model Name See this page for details
Certification or Licensing Information Required by Law See this page for details
Country of Manufacture or Origin See this page for details
Manufacturer See this page for details
After-sales Service Contact or Customer Support Number See this page for details

사용후기

등록된 사용후기

Be the first to leave a review!

상품문의

등록된 상품문의

Be the first to ask a question about this product!

배송정보

Service Information
 

교환/반품

Caution When Purchasing