​GE Fanuc (EMERSON) IC200ALG620 4-channel RTD input module uses 16-bit resolution for precision temperature sensing. The module supports 3-wire and 4-wire configurations, 0–3000 ohms range, 135 mA 5 VDC draw, and 60 ms rate, consult wiring and installation tips and confirm technical specifications sheets.
EMERSON: Product Insights  |  EMERSON: Technical Guides

상품 선택옵션 0 개, 추가옵션 0 개

Price US$1,316.67
Shipping Fee Paid at Checkout
Brand EMERSON
Model IC200ALG620
Availability In stock

선택된 옵션

  • EMERSON IC200ALG620
    +US$0.00
* Customs duties and VAT incurred during import clearance are the buyer's responsibility and are not included in the total amount.
위시리스트

상품 정보

상품 상세설명

OVERVIEW

Official designation: GE Fanuc IC200ALG620 (VersaMax, RTD Analog Input Module)

Role/Application: A 4-channel module for the VersaMax I/O system, providing 15 bits plus sign digital resolution for high-precision temperature sensing via various 3-wire or 4-wire RTD types.

KEY SPECS SUMMARY

Power: 125 mA maximum from plus 5V bus

Interfaces / Ports: VersaMax I/O carrier

Indicators: One OK LED (green for power, amber for fault)

Operating Temp: 0 degrees C to 60 degrees C

Platform / Compatibility: VersaMax I/O, CPU firmware 1.10 or higher

Limit: Maximum lead resistance is 50 ohms per lead

Lifecycle: Active

FREQUENTLY ASKED QUESTIONS

Technical Specifications:

Q: What are the two primary resistance ranges configurable for the RTD channels?

A: The configurable resistance ranges for each channel are 0 to 500 ohms or 0 to 3000 ohms.

Wiring & Installation:

Q: Is an external power supply required for the RTD excitation current on the module?

A: No, the module provides the necessary excitation current internally when configured for the specific RTD type.

Troubleshooting & Compatibility:

Q: What types of faults and diagnostic alarms does the module report?

A: It reports open RTD, input short, under/over range, and high/low alarm conditions.

Replacement & Upgrades:

Q: What is the rated accuracy for resistance or temperature measurement at 25 degrees C?

A: The accuracy is plus/minus 0.15 percent on both resistance and RTD temperature measurement.

상품 정보 고시

Category Details
Product Name See this page for details
Model Name See this page for details
Certification or Licensing Information Required by Law See this page for details
Country of Manufacture or Origin See this page for details
Manufacturer See this page for details
After-sales Service Contact or Customer Support Number See this page for details

사용후기

등록된 사용후기

Be the first to leave a review!

상품문의

등록된 상품문의

Be the first to ask a question about this product!

배송정보

Service Information
 

교환/반품

Caution When Purchasing