GE Fanuc (EMERSON) IC694ALG221 analog input module ensures precise signal acquisition via 4 channels for process monitoring efficiency. The RX3i unit accepts 0–20 mA or 4–20 mA current signals with 12-bit resolution and 4 uA precision, review technical specifications and wiring and installation guides for dependable system integration.
EMERSON: Product Insights  |  EMERSON: Technical Guides

상품 선택옵션 0 개, 추가옵션 0 개

Price US$1,483.33
Shipping Fee Paid at Checkout
Brand EMERSON
Model IC694ALG221
Availability In stock

선택된 옵션

  • EMERSON IC694ALG221
    +US$0.00
* Customs duties and VAT incurred during import clearance are the buyer's responsibility and are not included in the total amount.
위시리스트

상품 정보

상품 상세설명

OVERVIEW

Official designation: GE Fanuc IC694ALG221 (PACSystems RX3i, Analog Input Module)

Role/Application: Four-channel current input module for the RX3i system, designed for precise process monitoring by accepting 0 to 20 mA or 4 to 20 mA signals with optical isolation from field to backplane.

KEY SPECS SUMMARY

Power: 25 mA from 5 VDC, 100 mA from 24 VDC Isolated

Interfaces / Ports: Terminal block for I/O connection

Indicators: Module OK LED only

Operating Temp: 0 degrees C to 60 degrees C

Platform / Compatibility: PACSystems RX3i Universal Backplane

Limit: 200 Volts common mode voltage

Lifecycle: Active or Discontinued, varies by model/revision

FREQUENTLY ASKED QUESTIONS

Technical Specifications:

Q: What are the specific resolution values for the two input current ranges on the module?

A: Resolution is 4 microamperes per count for 4 to 20 mA and 5 microamperes per count for 0 to 20 mA.

Wiring & Installation:

Q: What type of cable is recommended for connecting field devices to the module inputs?

A: Use high-grade twisted, protected instrumentation cable for proper noise and capacitive issue reduction.

Troubleshooting & Compatibility:

Q: What is the maximum update rate for all four input channels on this module?

A: All four channels have a combined maximum update rate of 2 milliseconds.

Replacement & Upgrades:

Q: How is the input range selected between 0 to 20 mA and 4 to 20 mA?

A: Input range selection is achieved by installing or removing two range jumpers located on the I/O terminal panel.

상품 정보 고시

Category Details
Product Name See this page for details
Model Name See this page for details
Certification or Licensing Information Required by Law See this page for details
Country of Manufacture or Origin See this page for details
Manufacturer See this page for details
After-sales Service Contact or Customer Support Number See this page for details

사용후기

등록된 사용후기

Be the first to leave a review!

상품문의

등록된 상품문의

Be the first to ask a question about this product!

배송정보

Service Information
 

교환/반품

Caution When Purchasing