Official designation: Allen-Bradley 1732D-8I8O1212D (ArmorBlock I/O, Digital Combination Block)
Role/Application: A rugged, 16-point digital I/O block with 8 sink inputs and 8 source outputs for DeviceNet networks. This module is network-powered and features M12 connectors for distributed on-machine control.
KEY SPECS SUMMARY
Power: 24V DC nominal, network-powered I/O
Interfaces / Ports: M12 5-pin DeviceNet port, eight M12 I/O ports
Indicators: NET, MOD, and per-point I/O status LEDs
Operating Temp: -20 degrees C to 60 degrees C
Platform / Compatibility: DeviceNet, IP67/69K, on-machine mounting
Limit: 0.5 Amps per output, 2.2 Watts power consumption
Lifecycle: Active Mature
FREQUENTLY ASKED QUESTIONS
Technical Specifications:
Q: What is the maximum current draw of the module for its own operation and I/O?
A: The module's maximum network current draw is 0.1 Amps plus the I/O current, up to 5.0 Amps.
Wiring & Installation:
Q: Which connector type is utilized on the 1732D-8I8O1212D for I/O connections?
A: All eight I/O ports utilize DC Micro (M12) connectors.
Troubleshooting & Compatibility:
Q: What does a flashing red indication on the Network Status LED typically signify?
A: Flashing red indicates a recoverable fault, such as a timed-out I/O connection.
Replacement & Upgrades:
Q: What older Allen-Bradley module series can the 1732D DeviceNet block potentially replace?
A: This block is noted as a replacement for certain discontinued 1792D series modules.
상품 정보 고시
| Category | Details |
|---|---|
| Product Name | See this page for details |
| Model Name | See this page for details |
| Certification or Licensing Information Required by Law | See this page for details |
| Country of Manufacture or Origin | See this page for details |
| Manufacturer | See this page for details |
| After-sales Service Contact or Customer Support Number | See this page for details |
사용후기
등록된 사용후기
Be the first to leave a review!
상품문의
등록된 상품문의
Be the first to ask a question about this product!
배송정보

교환/반품