Official designation: Allen-Bradley 140U-D6D3-C10 (Bulletin 140U-D, Molded Case Circuit Breaker)
Role/Application: D-Frame, 3-pole current limiting thermal-magnetic MCCB with a fixed 10 A rated current for industrial low-voltage short-circuit and overcurrent protection.
KEY SPECS SUMMARY
Power: 600 Volts AC maximum
Interfaces / Ports: Screw terminals for copper wire
Indicators: Trip status flag
Operating Temp: Minus 25 to plus 60 degrees C
Platform / Compatibility: D-Frame; UL 489, CSA, IEC 60947-2
Limit: Magnetic trip fixed at 15 to 20 times rated current
Lifecycle: Discontinued by manufacturer
FREQUENTLY ASKED QUESTIONS
Technical Specifications:
Q: What is the high interrupting capacity of this 10 Amp D-Frame MCCB at 480 Volts AC?
A: The breaker provides a high Interrupting Rating of 100 kA at 480 Volts AC.
Wiring & Installation:
Q: What is the recommended tightening torque for the line and load terminals on this D-Frame unit?
A: The required tightening torque is 2.0 to 2.5 Newton meters or 18 to 22 pound inches.
Troubleshooting & Compatibility:
Q: Does the 140U-D6D3-C10 include a built-in mechanism for phase-loss protection?
A: This breaker does not have integrated phase-loss protection and requires external devices.
Replacement & Upgrades:
Q: What is the typical modern Allen-Bradley replacement series for the discontinued Bulletin 140U MCCB line?
A: The Bulletin 140G Molded Case Circuit Breaker series is the suggested current replacement product family.
상품 정보 고시
| Category | Details |
|---|---|
| Product Name | See this page for details |
| Model Name | See this page for details |
| Certification or Licensing Information Required by Law | See this page for details |
| Country of Manufacture or Origin | See this page for details |
| Manufacturer | See this page for details |
| After-sales Service Contact or Customer Support Number | See this page for details |
사용후기
등록된 사용후기
Be the first to leave a review!
상품문의
등록된 상품문의
Be the first to ask a question about this product!
배송정보

교환/반품