상품 정보
상품 상세설명
OVERVIEW
Official designation: SIEMENS 3RV6011-1HA15 (3RV6011 Series, Motor Protection Circuit Breaker)
Role/Application: Circuit breaker size S00 for motor protection, providing thermal overload (Class 10) and instantaneous short-circuit protection for industrial motors up to 3 kW at 400 V AC.
KEY SPECS SUMMARY
Power: Max operating voltage 690 V
Interfaces / Ports: Screw connection terminals
Indicators: Trip indicator not included
Operating Temp: Minus 20 degrees C to 60 degrees C
Platform / Compatibility: DIN rail mounting, IP20 front rating
Limit: Thermal release 5.5 to 8 A, N-release 104 A
Lifecycle: Active Product, replacement is 3RV2011-1HA15 (3RV2)
FREQUENTLY ASKED QUESTIONS
Technical Specifications:
Q: What is the rated short-circuit breaking capacity at 400 V?
A: The standard short-circuit breaking capacity is 100 kA at 400 V AC.
Wiring & Installation:
Q: What is the maximum recommended cable size for the main circuit screw terminals?
A: The main circuit screw terminals accept solid or stranded cable up to 6 square millimeters.
Troubleshooting & Compatibility:
Q: What is the main characteristic of the N-release instantaneous short-circuit protection?
A: The N-release is set at a fixed value of 104 A for reliable and fast short-circuit tripping.
Replacement & Upgrades:
Q: Which modern device is the primary replacement for the discontinued 3RV6011-1HA15 model?
A: The direct successor and replacement is the SIRIUS 3RV2011-1HA15 circuit breaker from the 3RV2 family.
상품 정보 고시
| Category | Details |
|---|---|
| Product Name | See this page for details |
| Model Name | See this page for details |
| Certification or Licensing Information Required by Law | See this page for details |
| Country of Manufacture or Origin | See this page for details |
| Manufacturer | See this page for details |
| After-sales Service Contact or Customer Support Number | See this page for details |
사용후기
등록된 사용후기
Be the first to leave a review!
상품문의
등록된 상품문의
Be the first to ask a question about this product!
배송정보

교환/반품