EMERSON IC200MDL730

GE Fanuc (EMERSON) IC200MDL730 VersaMax discrete output module features 8 positive logic outputs (sourcing) operating from 17.5 to 30 VDC. The unit has a fast 0.5 ms response and requires an 18-30 VDC external supply; consult the technical specifications and wiring and installation guide for deployment.
EMERSON: Product Insights  |  EMERSON: Technical Guides

상품 선택옵션 0 개, 추가옵션 0 개

Price US$741.67
Shipping Fee Paid at Checkout
Brand EMERSON
Model IC200MDL730
Availability In stock

선택된 옵션

  • EMERSON IC200MDL730
    +US$0.00
* Customs duties and VAT incurred during import clearance are the buyer's responsibility and are not included in the total amount.
위시리스트

상품 정보

상품 상세설명

OVERVIEW

Official designation: GE Fanuc IC200MDL730 (VersaMax, Discrete Output Module)

Role/Application: The IC200MDL730 is an 8-point discrete output module for VersaMax systems. It provides 24 VDC positive logic sourcing outputs with electronic short circuit protection (ESCP) for industrial loads.

KEY SPECS SUMMARY

Power: 5 VDC at 50 mA backplane

Interfaces / Ports: 8 sourcing output points

Indicators: OK, FLD PWR, 8 per-point LEDs

Operating Temp: 0 degrees C to 60 degrees C

Platform / Compatibility: VersaMax PLC or I/O Station

Limit: 2 Amps per point, 8 Amps per module

Lifecycle: Active, varies by revision

FREQUENTLY ASKED QUESTIONS

Technical Specifications:

Q: What are the nominal and maximum voltages required for the external field power supply?

A: The external field power supply requires 18 to 30 VDC, with 24 VDC being the nominal voltage.

Wiring & Installation:

Q: What is the required power-up sequence for the backplane and field power supplies?

A: Backplane power must be stable for a minimum of one second before applying field power.

Troubleshooting & Compatibility:

Q: What type of diagnostic faults are detected by the module and indicated by the amber LEDs?

A: The module provides point-level diagnostics for overload and short circuit conditions.

Replacement & Upgrades:

Q: Does this discrete output module support channel to channel or group to group isolation?

A: No, the IC200MDL730 does not provide either channel to channel or group to group isolation.

상품 정보 고시

Category Details
Product Name See this page for details
Model Name See this page for details
Certification or Licensing Information Required by Law See this page for details
Country of Manufacture or Origin See this page for details
Manufacturer See this page for details
After-sales Service Contact or Customer Support Number See this page for details

사용후기

등록된 사용후기

Be the first to leave a review!

상품문의

등록된 상품문의

Be the first to ask a question about this product!

배송정보

Service Information
 

교환/반품

Caution When Purchasing