EMERSON IC200MDL636

GE Fanuc (EMERSON) IC200MDL636 VersaMax DC Input Module handles high-density signal acquisition with 32 points on 24 VDC nominal power. The module supports selectable sourcing/sinking logic, 100 mA consumption, and 1 ms delay; access technical specifications for accurate wiring and installation details.
EMERSON: Product Insights  |  EMERSON: Technical Guides

상품 선택옵션 0 개, 추가옵션 0 개

Price US$833.33
Shipping Fee Paid at Checkout
Brand EMERSON
Model IC200MDL636
Availability In stock

선택된 옵션

  • EMERSON IC200MDL636
    +US$0.00
* Customs duties and VAT incurred during import clearance are the buyer's responsibility and are not included in the total amount.
위시리스트

상품 정보

상품 상세설명

OVERVIEW

Official designation: GE Fanuc IC200MDL636 (VersaMax, Discrete Input Module)

Role/Application: This 32-point input module is designed for high-density signal acquisition, supporting 48 VDC positive/negative logic, commonly used in high-voltage DC sensing applications.

KEY SPECS SUMMARY

Power: Nominal 48 VDC (0 to 60 VDC range)

Interfaces / Ports: Four 8-point groups to carrier

Indicators: 32 per-point LEDs, OK LED

Operating Temp: 0 degrees C to 60 degrees C

Platform / Compatibility: VersaMax I/O Carrier required

Limit: On-state 34 to 60 VDC

Lifecycle: Active (Refer to the latest manufacturer manual.)

FREQUENTLY ASKED QUESTIONS

Technical Specifications:

Q: What is the factory default filter time setting for this input module?

A: The input filter time is configurable from 0 to 7 milliseconds, with a 1 millisecond default.

Wiring & Installation:

Q: What are the minimum and maximum wire sizes accepted by the terminal base connectors?

A: Terminals accept AWG #24 to AWG #12 wire, solid or stranded, with certain limits for two wires.

Troubleshooting & Compatibility:

Q: Does the module provide isolation between every single input point on the unit?

A: No, isolation is provided only between the four 8-point groups and between the groups and backplane.

Replacement & Upgrades:

Q: What is the module's primary nominal voltage, and can it be used with 24 VDC sensors?

A: The nominal voltage is 48 VDC, but the 0 to 60 VDC range allows use with 24 VDC sources.

상품 정보 고시

Category Details
Product Name See this page for details
Model Name See this page for details
Certification or Licensing Information Required by Law See this page for details
Country of Manufacture or Origin See this page for details
Manufacturer See this page for details
After-sales Service Contact or Customer Support Number See this page for details

사용후기

등록된 사용후기

Be the first to leave a review!

상품문의

등록된 상품문의

Be the first to ask a question about this product!

배송정보

Service Information
 

교환/반품

Caution When Purchasing