GE Fanuc (EMERSON) IC694MDL741 Discrete Output Module ensures dependable DC output switching and modular scalability for discrete control applications in industrial automation. It delivers 16 isolated negative logic channels with 0.5 A per channel max current and draws 110 mA from the backplane; verify all technical specifications before completing wiring and installation procedures for reliable module performance.
EMERSON: Product Insights  |  EMERSON: Technical Guides

상품 선택옵션 0 개, 추가옵션 0 개

Price US$683.33
Shipping Fee Paid at Checkout
Brand EMERSON
Model IC694MDL741
Availability In stock

선택된 옵션

  • EMERSON IC694MDL741
    +US$0.00
* Customs duties and VAT incurred during import clearance are the buyer's responsibility and are not included in the total amount.
위시리스트

상품 정보

상품 상세설명

OVERVIEW

Official designation: GE Fanuc IC694MDL741 (PACSystems RX3i, Discrete Output Module)

Role/Application: A 16-point, 12/24 VDC, 0.5 A negative logic output module providing isolated DC output switching for industrial automation control applications within the RX3i system.

KEY SPECS SUMMARY

Power: 110 mA from 5VDC backplane

Interfaces / Ports: Terminal block (36 screws total)

Indicators: 16 individual channel LEDs

Operating Temp: Minus 20 degrees C to plus 60 degrees C

Platform / Compatibility: RX3i Universal Backplanes

Limit: 0.5 A per point / 2 A per group

Lifecycle: Active

FREQUENTLY ASKED QUESTIONS

Technical Specifications:

Q: What is the maximum voltage drop across a single output channel in the module?

A: The maximum output voltage drop is 0.5 volts when the channel is under the rated load.

Wiring & Installation:

Q: How many output groups does the IC694MDL741 module contain for field wiring?

A: The module contains 16 output points organized into two isolated groups of eight outputs.

Troubleshooting & Compatibility:

Q: What is the isolation voltage rating between field outputs and the backplane or frame ground?

A: Isolation is 250 VAC continuous and 1500 VAC for one minute.

Replacement & Upgrades:

Q: What is the maximum response time for the output to switch on or off after a command?

A: The maximum on response time is 2 milliseconds, and the maximum off response time is 2 milliseconds.

상품 정보 고시

Category Details
Product Name See this page for details
Model Name See this page for details
Certification or Licensing Information Required by Law See this page for details
Country of Manufacture or Origin See this page for details
Manufacturer See this page for details
After-sales Service Contact or Customer Support Number See this page for details

사용후기

등록된 사용후기

Be the first to leave a review!

상품문의

등록된 상품문의

Be the first to ask a question about this product!

배송정보

Service Information
 

교환/반품

Caution When Purchasing