GE Fanuc (EMERSON) IC694MDL250 VAC Discrete Input Module features 16 individually isolated channels for 120 VAC nominal operation in RX3i systems. The module supports a 0–132 VAC range with 60 mA from 5 VDC and provides enhanced signal reliability, offering essential wiring and installation guidelines for troubleshooting and compatibility.
EMERSON: Product Insights  |  EMERSON: Technical Guides

상품 선택옵션 0 개, 추가옵션 0 개

Price US$1,166.67
Shipping Fee Paid at Checkout
Brand EMERSON
Model IC694MDL250
Availability In stock

선택된 옵션

  • EMERSON IC694MDL250
    +US$0.00
* Customs duties and VAT incurred during import clearance are the buyer's responsibility and are not included in the total amount.
위시리스트

상품 정보

상품 상세설명

OVERVIEW

Official designation: GE Fanuc IC694MDL250 (PACSystems RX3i, AC Discrete Input Module)

Role/Application: Isolated 16-point input module for the RX3i platform, processing 120 VAC nominal field signals and providing transient electrical noise protection.

KEY SPECS SUMMARY

Power: 220 mA at 5 VDC bus

Interfaces / Ports: Box or spring clip terminal block

Indicators: Sixteen channel status LEDs

Operating Temp: 0 to 60 degrees C

Platform / Compatibility: RX3i Universal Backplane

Limit: 7.0 mA per point at 120 VAC

Lifecycle: Active

FREQUENTLY ASKED QUESTIONS

Technical Specifications:

Q: What is the maximum off-state leakage current and voltage for the IC694MDL250 module?

A: The maximum off-state leakage current is 2.5 mA and the voltage range is 0 to 20 VAC.

Wiring & Installation:

Q: What response times govern the switching behavior of the input module?

A: Maximum response times are 30 ms for turn-on and 45 ms for turn-off.

Troubleshooting & Compatibility:

Q: Can the input filter time of the 16 channels be adjusted and what is the typical range?

A: Yes, the filter time is adjustable from 20 ms to 2540 ms in 20 ms increments via the CPU.

Replacement & Upgrades:

Q: What is the continuous isolation rating between the field side and the backplane logic side?

A: The continuous isolation rating is 250 VAC, with a test voltage of 1500 VAC for one minute.

상품 정보 고시

Category Details
Product Name See this page for details
Model Name See this page for details
Certification or Licensing Information Required by Law See this page for details
Country of Manufacture or Origin See this page for details
Manufacturer See this page for details
After-sales Service Contact or Customer Support Number See this page for details

사용후기

등록된 사용후기

Be the first to leave a review!

상품문의

등록된 상품문의

Be the first to ask a question about this product!

배송정보

Service Information
 

교환/반품

Caution When Purchasing