GE Fanuc (EMERSON) IC695ALG808 isolated analog output module provides precise signal generation across 8 channels for advanced process control systems. The RX3i unit supports 0–20 mA and 10 V outputs with 15-bit resolution and requires external 24 VDC, review technical specifications and wiring and installation details for dependable system operation.
EMERSON: Product Insights  |  EMERSON: Technical Guides

상품 선택옵션 0 개, 추가옵션 0 개

Price US$5,041.67
Shipping Fee Paid at Checkout
Brand EMERSON
Model IC695ALG808
Availability In stock

선택된 옵션

  • EMERSON IC695ALG808
    +US$0.00
* Customs duties and VAT incurred during import clearance are the buyer's responsibility and are not included in the total amount.
위시리스트

상품 정보

상품 상세설명

OVERVIEW

Official designation: GE Fanuc IC695ALG808 (PACSystems RX3i, Isolated Analog Output Module)

Role/Application: Single-slot module for the RX3i Universal Backplane, providing eight isolated output channels configurable for voltage (+/- 10 V) or current (0-20 mA, 4-20 mA) for precise process control.

KEY SPECS SUMMARY

Power: 250 mA @ 3.3 V, 17 mA @ 5 VDC, 660 mA 24 VDC external

Interfaces / Ports: Compatible with IC694TBB/TBS032/132 terminal blocks (separate)

Indicators: MODULE OK LED (Green), FIELD STATUS LED (Green/Red)

Operating Temp: 0 degrees C to 60 degrees C

Platform / Compatibility: PACSystems RX3i Universal Backplane, CPU firmware 5.0 or later

Limit: 15-bit resolution (current and +/-10V), 14-bit (0-10V)

Lifecycle: Active or Discontinued, varies by model/revision

FREQUENTLY ASKED QUESTIONS

Technical Specifications:

Q: What is the maximum resistive load supported for the 4-20 mA current output?

A: The current output load resistance must not exceed 1350 Ohms maximum.

Wiring & Installation:

Q: Does the IC695ALG808 receive 24 VDC field power through the RX3i backplane?

A: No, the module requires the external 24 VDC field power to be wired directly to the terminal block.

Troubleshooting & Compatibility:

Q: What is the required configuration software version for this analog output module?

A: Machine Edition Version 5.7 SP3 Logic Developer-PLC or later is required for configuration.

Replacement & Upgrades:

Q: What is the isolation voltage rating between the field and backplane on the ALG808?

A: The module provides 2550 VDC isolation for one second between field and backplane.

상품 정보 고시

Category Details
Product Name See this page for details
Model Name See this page for details
Certification or Licensing Information Required by Law See this page for details
Country of Manufacture or Origin See this page for details
Manufacturer See this page for details
After-sales Service Contact or Customer Support Number See this page for details

사용후기

등록된 사용후기

Be the first to leave a review!

상품문의

등록된 상품문의

Be the first to ask a question about this product!

배송정보

Service Information
 

교환/반품

Caution When Purchasing