EMERSON IC695ALG616 요약정보 및 구매

GE Fanuc (EMERSON) IC695ALG616 analog input module provides 16 single-ended/8 differential channels for precise industrial measurement. The RX3i unit supports 0–20 mA and 10 V inputs with a 24-bit ADC, review technical specifications and wiring and installation details for dependable system integration.
EMERSON: Product Insights  |  EMERSON: Technical Guides

상품 선택옵션 0 개, 추가옵션 0 개

Price US$3,358.33
Shipping Fee Paid at Checkout
Brand EMERSON
Model IC695ALG616
Availability In stock

선택된 옵션

  • EMERSON IC695ALG616
    +US$0.00
* Customs duties and VAT incurred during import clearance are the buyer's responsibility and are not included in the total amount.
위시리스트

상품 정보

상품 상세설명

OVERVIEW

Official designation: GE Fanuc IC695ALG616 (PACSystems RX3i, Analog Input Module)

Role/Application: This non-isolated module provides 16 single-ended or 8 differential channels for high-resolution measurement of various voltage and current analog signals within the RX3i platform.

KEY SPECS SUMMARY

Power: 5V at 600mA, 3.3V at 450mA from backplane

Interfaces / Ports: Requires separate 32-point terminal block

Indicators: N/A

Operating Temp: 0 to 60 degrees C

Platform / Compatibility: PACSystems RX3i, firmware 3.0 or later

Limit: Overvoltage to plus/minus 60 VDC continuous

Lifecycle: Active, manufactured by Emerson Automation

FREQUENTLY ASKED QUESTIONS

Technical Specifications:

Q: What are the primary current and voltage input signal ranges supported by this module?

A: Supported current ranges are 0 to 20 mA, 4 to 20 mA, and plus/minus 20 mA.

Wiring & Installation:

Q: Which separate terminal block types are compatible with the IC695ALG616 module?

A: Compatible blocks include the box-style (IC694TBB032) and spring-style (IC694TBS032) versions.

Troubleshooting & Compatibility:

Q: What is the ADC conversion resolution and the typical common mode noise rejection?

A: The module features a 24-bit ADC and provides common mode rejection exceeding 120 dB at 50/60 Hz.

Replacement & Upgrades:

Q: What software version is required to configure the IC695ALG616 module in the PLC program?

A: Configuration requires Machine Edition Version 5.0 SP3 Logic Developer-PLC or later.

상품 정보 고시

Category Details
Product Name See this page for details
Model Name See this page for details
Certification or Licensing Information Required by Law See this page for details
Country of Manufacture or Origin See this page for details
Manufacturer See this page for details
After-sales Service Contact or Customer Support Number See this page for details

사용후기

등록된 사용후기

Be the first to leave a review!

상품문의

등록된 상품문의

Be the first to ask a question about this product!

배송정보

Service Information
 

교환/반품

Caution When Purchasing