GE Fanuc (EMERSON) IC694MDL940 Discrete Output Module provides 16 NO isolated contact outputs, supporting 5–250 VAC/DC switching at 2 amps per output and 4 amps per common, with a minimum electrical lifespan of 500,000 operations. Review the complete technical specifications for bus current draw details and consult the official wiring and installation guides for proper configuration of the four output groups and external fusing requirements.
EMERSON: Product Insights  |  EMERSON: Technical Guides

상품 선택옵션 0 개, 추가옵션 0 개

Price US$1,208.33
Shipping Fee Paid at Checkout
Brand EMERSON
Model IC694MDL940
Availability In stock

선택된 옵션

  • EMERSON IC694MDL940
    +US$0.00
* Customs duties and VAT incurred during import clearance are the buyer's responsibility and are not included in the total amount.
위시리스트

상품 정보

상품 상세설명

OVERVIEW

Official designation: GE Fanuc IC694MDL940 (PACSystems RX3i, Relay Output Module)

Role/Application: A 16-point discrete output module providing isolated normally open (NO) relay contacts for switching AC or DC loads in the RX3i system.

KEY SPECS SUMMARY

Power: 7 mA from 5V bus

Interfaces / Ports: 16 outputs / 4 commons

Indicators: One LED per point

Operating Temp: 0 degrees C to 60 degrees C

Platform / Compatibility: Universal RX3i slot

Limit: 2 A per output / 4 A per common

Lifecycle: Active

FREQUENTLY ASKED QUESTIONS

Technical Specifications:

Q: What is the maximum load current capacity for the entire IC694MDL940 module?

A: The total maximum load current capacity for the module is 16 Amps.

Wiring & Installation:

Q: What are the necessary isolation ratings for field wiring to the backplane?

A: Isolation is 250 VAC continuous and 1500 VAC transient for one minute.

Troubleshooting & Compatibility:

Q: What is the minimum load current required for reliable switching operation of the contacts?

A: The minimum load current required for proper operation of the relay contacts is 10 mA.

Replacement & Upgrades:

Q: What is the minimum expected electrical life of the output relay contacts?

A: The minimum electrical life of the isolated contacts is 500,000 operations.

상품 정보 고시

Category Details
Product Name See this page for details
Model Name See this page for details
Certification or Licensing Information Required by Law See this page for details
Country of Manufacture or Origin See this page for details
Manufacturer See this page for details
After-sales Service Contact or Customer Support Number See this page for details

사용후기

등록된 사용후기

Be the first to leave a review!

상품문의

등록된 상품문의

Be the first to ask a question about this product!

배송정보

Service Information
 

교환/반품

Caution When Purchasing