Official designation: GE Fanuc IC695ACC302 (PACSystems RX3i/RX7i, Auxiliary Smart Battery Module)
Role/Application: Provides extended volatile RAM memory backup and reliable low battery detection for PACSystems RX3i and RX7i controllers during power loss.
KEY SPECS SUMMARY
Power: 3 VDC output, 15.0 Ah capacity
Interfaces / Ports: Female 4-pin JAE connector
Indicators: Low-battery indication on compatible CPUs
Operating Temp: 0 to 60 degrees C
Platform / Compatibility: PACSystems RX3i, RX7i CPUs
Limit: Internal 1-Amp non-replaceable fuse
Lifecycle: 7 years nominal shelf life at 20 degrees C
FREQUENTLY ASKED QUESTIONS
Technical Specifications:
Q: What is the estimated volatile RAM retention period?
A: The retention period varies by CPU, ranging from 23 to 200 days at 20 degrees C.
Wiring & Installation:
Q: What is the recommended connection procedure to maximize service life?
A: Install the fresh battery after the connected CPU is powered ON to delay initial discharge.
Troubleshooting & Compatibility:
Q: Which version resolved the incorrect low-battery detection period issue?
A: The IC695ACC302-AB revision corrects the low-battery indication on supported CPUs.
Replacement & Upgrades:
Q: What is the direct predecessor module this unit enhances?
A: This module is the enhanced version, replacing the legacy auxiliary battery module IC693ACC302.
상품 정보 고시
| Category | Details |
|---|---|
| Product Name | See this page for details |
| Model Name | See this page for details |
| Certification or Licensing Information Required by Law | See this page for details |
| Country of Manufacture or Origin | See this page for details |
| Manufacturer | See this page for details |
| After-sales Service Contact or Customer Support Number | See this page for details |
사용후기
등록된 사용후기
Be the first to leave a review!
상품문의
등록된 상품문의
Be the first to ask a question about this product!
배송정보

교환/반품