Omron CS1W-ID211 DC input module provides 16 sink/source input points, operating at a rated 24 VDC with a max 15 ms response for precise monitoring. This flexible unit ensures stable 4.6 mA current and 15 VDC ON threshold, confirming technical specifications for your new wiring and installation project.
OMRON: Product Insights  |  OMRON: Technical Guides

상품 선택옵션 0 개, 추가옵션 0 개

Price US$758.33
Shipping Fee Paid at Checkout
Brand OMRON
Model CS1W-ID211
Availability In stock

선택된 옵션

  • OMRON CS1W-ID211
    +US$0.00
* Customs duties and VAT incurred during import clearance are the buyer's responsibility and are not included in the total amount.
위시리스트

상품 정보

상품 상세설명

OVERVIEW

Official designation: Omron CS1W-ID211 (CS1 Series, DC Input Unit)

Role/Application: This 16-point DC digital input module is utilized in CS1 series PLC racks to monitor 24 VDC sink or source external field devices for industrial control applications.

KEY SPECS SUMMARY

Input Points: 16 points

Input Type: DC Digital (Sink/Source)

Rated Input Voltage: 24 VDC

Input Voltage Range: 20.4 to 26.4 VDC

Input Current: 7 mA typical at 24 VDC

ON Voltage/Current: 14.4 VDC min / 3 mA min

OFF Voltage/Current: 5 VDC max / 1 mA max

Max ON/OFF Response Time: 8.0 ms (Default)

Internal Current Consumption: 0.1 A max at 5 VDC

Connection Type: Removable terminal block (M3 screws)

Operating Temp: 0 to 55 degrees C

Lifecycle: Active

FREQUENTLY ASKED QUESTIONS

Technical Specifications:

Q: What is the input impedance of the CS1W-ID211 module for calculating the current draw?

A: The input impedance of the module is specified as 3.3 k Ohm nominal.

Wiring & Installation:

Q: What is the primary connection method for field devices to the 16-point CS1W-ID211 module?

A: The unit connects using a removable terminal block with M3 screw terminals.

Troubleshooting & Compatibility:

Q: What is the acceptable maximum leakage current from an external device for the input to be considered OFF?

A: The maximum OFF current allowed to maintain an OFF state is 1 mA max.

Replacement & Upgrades:

Q: Can the CS1W-ID211 input unit replace input modules in the older Omron C200H PLC systems?

A: No, the CS1W-ID211 is exclusively designed for the Omron SYSMAC CS1 series and rack mounting.

상품 정보 고시

Category Details
Product Name See this page for details
Model Name See this page for details
Certification or Licensing Information Required by Law See this page for details
Country of Manufacture or Origin See this page for details
Manufacturer See this page for details
After-sales Service Contact or Customer Support Number See this page for details

사용후기

등록된 사용후기

Be the first to leave a review!

상품문의

등록된 상품문의

Be the first to ask a question about this product!

배송정보

Service Information
 

교환/반품

Caution When Purchasing