상품 정보
상품 상세설명
OVERVIEW
Official designation: SIEMENS 3RV1021-4AA10 (SIRIUS, Motor Protection Circuit Breaker)
Role/Application: Three-pole circuit breaker size S0 for motor protection against short circuits, overloads, and phase failures in industrial power systems up to 7.5 kW.
KEY SPECS SUMMARY
Power: Operating voltage up to 690 V
Interfaces / Ports: Screw type terminals
Indicators: Visible trip indication
Operating Temp: Minus 20 degrees C to 60 degrees C
Platform / Compatibility: DIN rail 35 mm mounting
Limit: Adjustable trip range 11 to 16 A
Lifecycle: Phased-out, successor is 3RV2021-4AA10
FREQUENTLY ASKED QUESTIONS
Technical Specifications:
Q: What is the short-circuit breaking capacity at 400 V AC for this device?
A: The maximum short-circuit current breaking capacity (Icu) at 400 V AC is 50 kA.
Wiring & Installation:
Q: What type of overload protection and short circuit release is integrated in the breaker?
A: The overcurrent and short circuit release mechanism is thermomagnetic.
Troubleshooting & Compatibility:
Q: Does the motor protection circuit breaker include auxiliary contacts as a standard feature?
A: The product extension for an auxiliary switch is available but must be added optionally.
Replacement & Upgrades:
Q: What is the preferred successor model for the 3RV1021-4AA10 and its product designation?
A: The preferred successor type is SIRIUS 3RV2021-4AA10, requiring review for differences.
상품 정보 고시
| Category | Details |
|---|---|
| Product Name | See this page for details |
| Model Name | See this page for details |
| Certification or Licensing Information Required by Law | See this page for details |
| Country of Manufacture or Origin | See this page for details |
| Manufacturer | See this page for details |
| After-sales Service Contact or Customer Support Number | See this page for details |
사용후기
등록된 사용후기
Be the first to leave a review!
상품문의
등록된 상품문의
Be the first to ask a question about this product!
배송정보

교환/반품